CHLORINE DIOXIDE EXPLOSION REMEDIATION

Location: Northwestern Georgia

Client: Major Water Treatment Authority

Contract Amount: $84,000

Dechlorination of Chlorine Dioxide with Sodium Metabisulfite and Soda Ash in Ice Bath

Dechlorination of Chlorine Dioxide with Sodium Metabisulfite and Soda Ash in Ice Bath

Chlorine Dioxide Explosion

Chlorine Dioxide Explosion

Municipal Water Treatment Chlorination Facility

Municipal Water Treatment Chlorination Facility



CHLORINE DIOXIDE EXPLOSION PROBLEM


Remtech was retained by a major water treatment authority to cleanup and determine the cause of a chlorine dioxide explosion which occurred at a raw water pumping station. Shock sensitive sodium chlorite burn residues remained in the building.


CHLORINE DIOXIDE EXPLOSION SOLUTION


A remediation plan was prepared to deactivate the reactor residues while keeping chlorine and chlorine dioxide ambient concentrations below detection limits. Bench-scale reactions were conducted to confirm full-scale reactions.


Forty gallons of burn residues were reacted with 200 pounds of soda ash and 100 pounds of sodium metabisulfite. Heat of reaction energy

was dissipated by placing 150 pounds of cubed ice in the reactors.


Reactions were conducted in closed poly reactors. Off gasses were collected and passed through two gas scrubbers with a soda ash/

sodium metabisulfite solution. Off gasses were monitored to ensure that no chlorine or chlorine dioxide was liberated from the reaction.


The temperature of the reaction vessels was monitored to keep temperatures below 120o F. Over two (2) tons of residual sodium chlorite were reacted.


The walls and floor were cleaned with a hot pressure washer. Wash water was collected and processed through the dechlorination reactors. Plastic components left a residue on the ceilings, glass block walls, and concrete floor. These residues were removed with caustic and acid cleaners.


CHLORINE DIOXIDE EXPLOSION REMEDIATION COST/BENEFITS


Remtech prepared an engineering report delineating the cause of the fire. A short in a PLC controller panel for a motorized control valve initiated a fire.


This report allowed the insurance company for the water utility to secure reimbursement (several hundred thousand dollars) from the

chlorine dioxide manufacturer’s insurance company.