Client: Air force Base
Location: Upper Peninsula, Michigan
Contract Amount: $280,000
Problem Definition:
- Military Petroleum, Oil & Lubricant Terminal
- 10 Acre Site
- 200+ Monitoring Wells
- Site Investigation by Others
- 2 to 3 ft of Free Product in Existing Wells
- 75,000 gallons of JP-4 Jet Fuel Estimated
- Objective - Free Product Recovery System Design, Installation,
& Operation
Design Information Available:
- No Aquifer Free Product Well Thickness Correction
- No Free Product Recharge/Mobility Rates
- No Sustainable Flowrates
- Pilot Test - 17 gpm & <5 gpd FPR
- Conductivities 10-3 to 10-6 cm/sec
- 3 Hr Pump Test - 0.5 ft drawdown 20 ft Away
Remtech Full-Scale Package Treatment Plants:
- Six 6-inch Recovery Wells
- Two Treatment Compounds
- Remtech Model 0.25 Slurp Recovery Well Pumps
- Oil/Water Separation
- Diffused Air Stripping
- Carbon Off-Gas Treatment
Remtech Treatment Plant Features:
- Gravity Feed Diffused Air Strippers
- No Metals Pretreatment
- Easy System Cleaning
- Freeze Protection
- Low-Maintenance Rotary Screw Compressors
|
|

Leaking Bulk Storage Facility

Remtech Groundwater Treatment System

Remtech Model 0.25 Slurp Pump |